Occupancy groups and construction types in the building code

Updated
Written by
Alexander J. Hale
Reading time
12 min
Sheet
36 of 44

The International Building Code (IBC) gives each space in a building an occupancy classification, one of ten lettered groups based on what people do there, from A for assembly to U for utility buildings such as sheds. It also gives the building a construction type, from Type I, built of materials that don’t burn and rated to hold up longest in a fire, to Type V, which may use any material the code allows, ordinary wood framing included. Read together, the two set the building’s limits on height, stories and floor area, and most of the fire ratings its walls and floors need.

The IBC occupancy classification chart

The groups exist because people get out of a fire at different speeds depending on where they are. A crowd in a dark theater, a hospital patient who can’t walk, a tenant asleep on the fourth floor and a hotel guest who has never seen the back stairs all need more time or more help than an office worker at a desk. The contents count too, since a warehouse full of tires carries far more fuel than one full of glass. Section 302.1 of the IBC sorts these situations into ten groups, six of which split into numbered subgroups. The International Code Council (ICC), which writes the IBC, counts 26 specific occupancies in all.

Group What it covers Subgroups and common examples named in the code
A, assembly People gathered for shows, food, worship or sport A-1 theaters and concert halls, usually with fixed seats. A-2 restaurants, bars, nightclubs and banquet halls. A-3 places of worship, libraries, museums, gyms without spectator seating. A-4 indoor arenas, rinks and pools with spectator seating. A-5 outdoor stadiums, grandstands and bleachers
B, business Offices and service transactions Offices, banks, outpatient clinics, barber shops, testing and research labs, classrooms for students past 12th grade, and assembly rooms for fewer than 50 people
E, educational Schools through 12th grade Schools used by six or more people at a time, and day care for more than five children older than 2½
F, factory Making, assembling and repairing things F-1 moderate hazard, such as bakeries and furniture or cabinet shops. F-2 low hazard, such as brick, glass products and ice
H, high hazard Hazardous materials above the amounts the code allows in a space H-1 explosives, H-2 flammable gases, H-3 flammable solids, H-4 corrosive and toxic materials, H-5 semiconductor fabrication
I, institutional People in supervised care or custody I-1 assisted living for more than 16 residents. I-2 hospitals and nursing homes. I-3 jails and prisons. I-4 day care for people of any age for less than 24 hours
M, mercantile Selling goods to the public Department stores, drugstores, markets, gas stations
R, residential Places where people sleep R-1 hotels and motels. R-2 apartments, dormitories and timeshares. R-3 buildings with no more than two dwelling units, and care homes for five or fewer people. R-4 supervised care for 6 to 16 residents
S, storage Warehouses and parking S-1 moderate hazard, such as furniture, tires and self-storage. S-2 low hazard, such as parking garages and stored food or glass
U, utility Accessory structures Private garages, carports, sheds, towers

The borders between neighboring groups are where classification goes wrong. A hotel and an apartment building can look the same from the street, and the code tells them apart by how long people stay, with R-1 for mostly short-term guests and R-2 for mostly permanent residents. A hospital and an outpatient clinic can look the same on a floor plan. The hospital is I-2 because its patients stay around the clock and many can’t save themselves, while the clinic, whose patients go home the same day, is B. An ICC training deck on occupancy classification opens its occupancy section with the line “Everything starts with the correct occupancy classification!”

Mixed occupancies and fire separation

Many buildings hold more than one group, a shop under apartments or an office inside a warehouse. Section 508 has the designer classify each space on its own, then pick one of three ways to handle the mix. The ICC notes that a designer may use more than one method in the same building.

Method What it means Fire separation between groups Height and area limits
Accessory occupancy A minor use that supports the main one, capped at 10 percent of the floor area of its story Generally none, except around apartments, hotel rooms and some hazardous uses Those of the main occupancy
Nonseparated occupancies The groups share space and are treated as one None required, with the same exceptions The strictest limit of any group present applies to the whole building, and so do the strictest sprinkler and alarm rules
Separated occupancies Each group is closed off from its neighbors by fire-rated walls or floors Rated in hours by Table 508.4 Each group keeps its own limits, and on each story the actual area of each group divided by its allowable area must add up to no more than 1

The trade term for a fire-rated wall that does this job is a fire barrier, and a rated floor doing the same job is a horizontal assembly. Table 508.4 sets the hours by pairing groups. In a building sprinklered throughout, apartments next to shops need a 1-hour separation, and without sprinklers the same pair needs 2 hours. The ICC calls the nonseparated method the most commonly used. It needs no rated walls between groups, and the price is living with the strictest limits.

One special case, explained on the page about 5-over-1 and podium buildings, gets a section of its own. Section 510.2 lets a concrete base and the floors above it count as two separate buildings when a 3-hour floor divides them and a short list of other conditions is met, the arrangement under apartment buildings that sit over a garage and shops.

Types of construction in the IBC

Occupancy describes the people. Construction type describes the building. It records whether the structure can burn and how long it must keep carrying its load in a fire. Chapter 6 sets five types. In Types I and II, the structural elements must be noncombustible, meaning steel, concrete or masonry. Type III requires noncombustible exterior walls, though fire-retardant-treated wood may frame exterior walls rated 2 hours or less, and allows any permitted material inside. Type IV is built of mass timber, which the code defines as solid, built-up, panelized or engineered wood thick enough to meet the type’s minimum sizes, or of noncombustible materials, and Type V may be built of anything the code permits.

Most types split again. In Types II, III and V, the A version is protected, meaning its frame, floors and roof must last a set number of hours in a standard furnace test, and the B version is unprotected, with no required rating for most of its structure. Both versions of Type I carry ratings, with I-A rated higher, and Type IV splits four ways, mostly by how much of its wood must be covered. Table 601 sets the hours.

Type What the structure may be Frame, floors, roof (hours of fire resistance, Table 601) Often seen in
I-A Noncombustible 3, 2, 1½ High-rises, hospitals, concrete podiums under apartments
I-B Noncombustible 2, 2, 1 Mid-rise and high-rise offices
II-A Noncombustible 1, 1, 1 Steel or concrete schools and offices
II-B Noncombustible 0, 0, 0 One-story steel-frame stores and warehouses
III-A Exterior walls noncombustible or of treated wood, any material inside 1, 1, 1 (exterior bearing walls 2) Masonry-walled main-street buildings, wood-frame apartments with treated-wood exterior walls
III-B Same as III-A 0, 0, 0 (exterior bearing walls 2) Same as III-A, with no rating inside
IV-A Mass timber, fully covered with noncombustible protection 3, 2, 1½ Tall mass timber buildings
IV-B Mass timber, mostly covered, with limited exposed areas 2, 2, 1 Mass timber offices and apartments
IV-C Mass timber that may be left exposed inside 2, 2, 1 Mass timber buildings with visible wood ceilings
IV-HT Large solid or glued-laminated timbers of minimum sizes, with noncombustible exterior walls Minimum timber sizes stand in for hours Old mills and warehouses, timber-frame buildings
V-A Any material the code permits 1, 1, 1 Wood-frame apartments, small offices and shops
V-B Any material the code permits 0, 0, 0 Small wood-frame buildings

The lower the Roman numeral, the more fire resistance the structure has, and the taller and larger the code lets it grow. Types IV-A, IV-B and IV-C entered the code in the 2021 edition to let mass timber reach as high as 18 stories in Type IV-A.

Type V construction

Section 602.5 lets a Type V building’s structure, exterior walls and interior walls be any material the code permits, which in practice usually means wood studs, joists and trusses. Type V-A needs 1 hour of fire resistance on its frame, bearing walls, floors and roof, usually reached by covering the wood with fire-rated gypsum board built to a tested design. Type V-B needs no rating at all, and the code makes up for that with the lowest height and area limits in the tables. Detached houses, duplexes and townhouses of up to three stories are usually built under a separate code, the International Residential Code, which doesn’t use these types.

How occupancy and construction type set allowable height and area

Every height and area limit sits at the crossing of an occupancy row and a construction type column, and the lookup runs in a fixed order.

  1. Classify each space by occupancy group, using Chapter 3.
  2. Choose a construction type, using Chapter 6.
  3. Read the allowable height in feet from Table 504.3 and the number of stories from Table 504.4, both measured from the ground around the building, which the code calls grade plane.
  4. Read the allowable floor area per story from Table 506.2, then add the frontage increase from Section 506.3 if at least 25 percent of the building’s perimeter faces a street or open space at least 20 feet wide.
  5. For a building of more than three stories, check that the total floor area stays within three times the per-story allowance.
  6. For more than one occupancy, apply the Section 508 method chosen above.

A fire wall that meets Section 706 splits a structure into separate buildings for this lookup, so one large building can be treated as two.

The biggest increases come from sprinklers. The tables print separate rows for buildings without sprinklers (NS), for buildings sprinklered throughout to the full standard, NFPA 13 (S), and for the lighter residential standard, NFPA 13R (S13R). In most columns, the full sprinkler row allows one more story and 20 more feet of height than the unsprinklered row. Its area factor is three times the unsprinklered figure for a building of several stories and four times for a one-story building. An office in Type V-A, for example, gets 3 stories, 50 feet and 18,000 square feet a story without sprinklers, and 4 stories, 70 feet and 54,000 square feet a story with them. The NFPA 13R row stops at 60 feet in every column, whatever the construction type. For apartments and hotels, the unsprinklered values are only for judging existing buildings, because Section 903.2.8 requires sprinklers throughout every new building with a Group R fire area.

Worked example: the code summary for 1200 Walnut Street

1200 Walnut Street, the fictional six-story building the book follows, shows how a single building collects several groups and two types. Its figures here, like everywhere in the book, are illustrative.

Part of the building Occupancy group Construction type
Levels 2 to 6, 200 apartments R-2 Wood frame, in a combustible type the code allows to that height with sprinklers
Level 1, street-level garage S-2 Concrete podium, Type I-A
Level 1, two retail shells M, or A-2 if a restaurant leases one Concrete podium, Type I-A

Section 510.2 lets the architect count the concrete level and the wood floors as two buildings for stories and construction type when, among other conditions, the deck between them is rated for 3 hours. That is an hour more than Table 601 asks of an ordinary Type I-A floor.

The retail shells are why the occupancy column gets rechecked at every lease. A store counts one person per 60 gross square feet and dining at tables one per 15 net, so 1,000 square feet of dining room holds about 67 people where the same floor as a shop holds about 17. The code caps a space with a single exit at 49 occupants in either use (Table 1006.2.1), so the dining room would need a second exit that the shop can do without, and with 50 or more inside, Section 1010.1.2.1 requires its doors to open toward the way out. The final answer goes on the certificate of occupancy, which by code states the occupancy classification and the construction type.

What newcomers get wrong

  1. Treating zoning use and building code occupancy as one system. Zoning decides whether a restaurant may open on the lot. The building code’s group decides how the space must be built once it does.
  2. Assuming a building has one occupancy. A shop under apartments, or an office inside a factory, makes it a mixed-occupancy building, and the code needs a method for the mix.
  3. Filing every gathering space under A. A building or tenant space used for assembly with fewer than 50 occupants is classified as Group B.
  4. Reading “unprotected” as unsafe or illegal. A Type V-B or II-B building is fully legal, and the code offsets its unrated structure with tighter limits on height and area.
  5. Citing “the IBC” with no edition. Each city adopts an edition on its own schedule, often with amendments, and section numbers and table values can differ between editions.

Where to look it up

In recent editions of the IBC, the sorting happens in three chapters near the front of the book. Chapter 3 holds the occupancy groups, Chapter 5 holds height, area, mixed occupancies and the podium rule, and Chapter 6 holds the construction types and Table 601. Sprinkler requirements are in Chapter 9. Start with the edition your city has adopted and its local amendments, which building departments usually post online. The ICC publishes the model codes at codes.iccsafe.org, and UpCodes posts many state and city adoptions with their amendments marked. Building departments often publish a short handout as well. The City of Las Vegas, for one, gives permit applicants a handout listing every 2021 IBC occupancy group with examples, followed by a plain description of the construction types.

On a real project, the answers are written on the code analysis, which the guide to reading construction drawings shows how to find. It is usually among the first sheets of the set, and it states each occupancy, the construction type, whether the building is sprinklered, and the allowable area beside the actual one.